My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
Ord 2019-011/Amendments to Chapter 38 - Fire Prevention and Protection of the San Marcos City Code of Ordinances
San-Marcos
>
City Clerk
>
02 Ordinances
>
2010's
>
2019
>
Ord 2019-011/Amendments to Chapter 38 - Fire Prevention and Protection of the San Marcos City Code of Ordinances
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
5/31/2019 3:45:16 PM
Creation date
5/17/2019 11:14:28 AM
Metadata
Fields
Template:
City Clerk
City Clerk - Document
Ordinances
City Clerk - Type
Amending
Number
2019-11
Date
5/7/2019
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
43
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
Show annotations
View images
View plain text
(For care of more than five children 2 1/2 or less years of age, see <br />Section 907.2.6.) {No change to remainder of exceptions.) <br />Section 907.2.13. Exception 3: change to read as follows: <br />3. Open air portions of buildings with an occupancy in Group A-5 in accordance <br />with Seciion 303.1 of the International Building Code, however, this exception <br />does not apply to accessory uses including but not limited to sky boxes, <br />restaurants, and similarly enclosed areas. <br />Section 907.4.2; add Section 907, 4.2.7 to read as follows: <br />907.4.2.7 Type. Manual alarm initiating devices shall be an approved double action <br />Section 907.6.1; add Section 907.6.1.1 to read as follows: <br />907.6.1.1 Wiring Installation. All fire alarm systems shall be installed in such a <br />manner that a failure of any single initiating device or single open in an initiating <br />circuit conductor will not interfere with the normal operation of other such devices. <br />All signaling line circuits (SLC) shall be installed in such a way that a single open <br />will not interfere with the operation of any addressable devices (Class A). Outgoing <br />and return SLC conductors shall be installed in accordance with NFPA 72 <br />requirements for Class A circuits and shall have a minimum of four feet separation <br />horizontal and one foot vertical between supply and return circuit conductors. The <br />initiating device circuit (IDC) from a signaling line circuit interface device maybe <br />wired Class B provided the distance from the interface device to the initiating <br />device is ten feet or less. <br />Section 907.6.3; delete all four Exceptions. <br />Section 909.22; add to read as follows: <br />909.22 Stairway or Ramp Pressurization Alternative. Where the building is <br />equipped throughout with an automatic sprinkler system in accordance with Section <br />903.3.1.1 and the stair pressurization alternative is chosen for compliance with <br />Building Code requirements for a smokeproof enclosure, interior exit stairway <br />ramps shall be pressurized to a minimum of 0.10 inches of water (25 Pa) and a <br />maximum of 0.35 inches of water (87 Pa) in the shaft relative to the building <br />measured with all interior exit stairway and ramp doors closed under maximum <br />anticipated conditions of stack effect and wind effect. Such systems shall comply <br />with Section 909, including the installation of a separate fire-fighter's smoke control <br />panel as per Section 909.16, and a Smoke Control Permit shall be required from the <br />fire department as per Section 105.7. <br />
The URL can be used to link to this page
Your browser does not support the video tag.