Section 1010.1.9.4 Bolt Locks; change Exceptions 3 and 4 to read as follows: <br />Exceptions: <br />3. Where a pair of doors serves an occupant load of less than 50 persons <br />in a Group B, F, M or S occupancy. {Remainder unchanged} <br />4. Where a pair of doors serves a Group A, B, F, M or S occupancy. <br />{Remainder unchanged) <br />Section 1015.8 Window Openings; change number I to read as follows: <br />1. Operable windows where the top of the sill of the opening is located more than <br />55 feet (16 764 mm) above the finished grade or other surface below and that <br />are provided with window fall prevention devices that comply with ASTM F <br />2006. <br />Section 1031.2; change to read as follows: <br />1031.2 Reliability. Required exit accesses, exits and exit discharges shall be <br />continuously maintained free from obstructions or impediments to full instant use <br />in the case of fire or other emergency. An exit or exit passageway shall not be used <br />for any purpose that interferes with a means of egress. <br />Section 1103.7, add Section 1103.7.8 and 1103.7,8.1 to read as follows: <br />1103.7.8 Fire Alarm System Design Standards. Where an existing fire alarm <br />system is upgraded or replaced, the devices shall be addressable. Fire alarms std <br />utilizing more than 20 smoke and/or heat detectors shall have analog initiating <br />devices. <br />Exception: Existing_ systems need not comply unless the total building, or <br />fire alarm system, remodel or expansion exceeds 30% of the building. When <br />cumulative building, or fire alarm system, remodel or expansion initiated <br />after the date of original fire alarm panel installation exceeds 50% of the <br />building, or fire alarm system, the fire alarm system must comply within 18 <br />months of permit application. <br />1103.7.8.1 Communication requirements. Refer to Section 907.6.6 for applicable <br />requirements. <br />Table 3206.2, footnote i; change text to read as follows: <br />j. Where storage areas are protected by either early suppression fast response <br />(ESFR) sprinkler systems or control mode special application sprinklers with a <br />response time index of 50 (m • s) 1/2 or less that are listed to control a fire in the <br />