Laserfiche WebLink
3. The attic space is a part of the building's thermal, or heat, envelope, such that insulation <br />is provided at the roof deck, rather than at the ceiling level. <br />903.3.1.4.2 Heat trace/insulation. Heat trace/insulation shall only be allowed where approved by the fire <br />code official for small sections of large diameter water -filled pipe. <br />Section 903.3.5; add a second paragraph to read as follows: <br />Water supply as required for such systems shall be provided in conformance with the supply requirements of the <br />respective NFPA standards; however, every water-based fire protection system shall be designed with a 5 psi safety <br />factor. Reference Section 507.4 for additional design requirements. <br />Section 903.4; add a second paragraph after the exceptions to read as follows: <br />Sprinkler and standpipe system water -flow detectors shall be provided for each floor tap to the sprinkler system and <br />shall cause an alarm upon detection of water flow for more than 45 seconds. All control valves in the sprinkler and <br />standpipe systems except for fire department hose connection valves shall be electrically supervised to initiate a <br />supervisory signal at the central station upon tampering. <br />Section 903.4.2; add second paragraph to read as follows: <br />The alarm device required on the exterior of the building shall be a weatherproof horn/strobe notification appliance <br />with a minimum 75 candela strobe rating, installed as close as practicable to the fire department connection. <br />Section 905.2; change to read as follows: <br />905.2 Installation Standard. Standpipe systems shall be installed in accordance with this section and NFPA 14. <br />Approved, locking caps shall be installed on all standpipe connections that are installed as a result of new <br />construction. Additionally, where remodeling of a building or structure requires the addition or alteration of a <br />standpipe system, locking caps shall be installed. Where standpipes exist on current buildings, but the caps are <br />missing or damaged, they must be replaced with locking caps, as approved by the fire code official. <br />Section 905.3.9; add to read as follows: <br />905.3.9 Buildings Exceeding 10,000 sq. ft. In buildings exceeding 10,000 square feet in area per story and where any <br />portion of the building's interior area is more than 200 feet (60960 mm) of travel, vertically and horizontally, from <br />the nearest point of fire department vehicle access, Class I automatic wet or manual wet standpipes shall be <br />provided. <br />Exceptions: <br />1. Automatic dry, semi-automatic dry, and manual dry standpipes are allowed as provided for in NFPA 14 <br />where approved by the fire code official. <br />2. R-2 occupancies of four stories or less in height having no interior corridors. <br />Section 905.4; change Items 1, 3, and 5, and add Item 7 to read as follows: <br />1. In every required interior exit stairway, a hose connection shall be provided for each story above and below <br />grade plane. Hose connections shall be located at an intermediate landing between stories, unless otherwise <br />approved by the fire code official. <br />Exception: {No change.} <br />2. {No change.} <br />3. In every exit passageway, at the entrance from the exit passageway to other areas of a building. <br />(Supp. No. 35, Update 4) <br />Page 13 of 44 <br />Created: 2022-12-02 10:13:41 [EST] <br />