Laserfiche WebLink
City of San Marcos <br />SCADA System I/O <br /> <br />Site Location: Comanche Pump Station RTU No. 103 <br /> <br />:unction Mod'ules: PLC001 Enclosure: Stainless Qty Function Slots <br />)CM003-1=A, DMM002=B NEMA 4X 48Hx36Wx10D 1 Qty Used . .Spare <br />~,MM002=CDE MBP001 2 10 6 4 <br /> <br /> ' 'S i g n a I's . system <br />Function Condition Al I AO J DI ' 1 DO address <br />BOOSTER P1 CAEL STOP/START 1 103A1 <br />BOOSTER P2 CALL STOP/START 1 103A2 <br />BOOSTER P3 CALL STOP/START .' I 103A3 <br />BOOSTER P4 CALL STOP/START 1 103A4 <br />BOOSTER P1 RUNS STOPPED/RUNNING I 103B1 <br />BOOSTER P2 RUNS STOPPED/RUNNING 1 103B2 <br />BOOSTER P3 RUNS STOPPED/RUNNING 1 103B3 <br />BOOSTER P4 RUNS STOPPED/RUNNING. 1 103B4 <br />BOOSTER P1 HOA AUTO OTHER/AUTO I 103B5 <br />BOOSTER P2 HOA AUTO OTHER/AUTO 1 103B6 <br />BOOSTER P3 HoA AUTO OTHER/AUTO 1 103B7 <br />BOOSTER P4 HOA AUTO OTHER/AUTO 1 103B8 <br />CHE i(VALVE OPEN/CLOSE I 103B9 <br />CH[: :~INE DETECT OK/DETECT 1 '103B10 <br />INTF, uSION INTRUSION/OK i I 103B11 <br />GST LEVEL 0/100% 1 103C1 <br />SYSTEM PRESSURE 0/100% 1 103C2 <br />BOOSTER P1 AMPS 0/100% 1 103C3 <br />BOOSTER P2 AMPS 0/100% 1 103C4 <br />BOOSTER P3 AMPS 0/100% I 103D1 <br />BOOSTER P4 AMPS 0/100% 1 103D2 <br />DISCHARGE FLOW 0/100% 1 103D3 <br />CHLORINE RESIDUAL FREE 0/100% 1 103D4 <br />CHLORINE RESIDUAL TOTAL 0/100% 1 103E1' <br />RTU DC FAULT FAULT/OK INTERNAL- 103R11 <br />RTU AC FAULT FAULT/OK INTERNAL 103R12 <br />SPARE 3 0 5 4 <br /> <br /> <br />