Laserfiche WebLink
709. 10 Fire partitions shall be installed in R -2 occupancies in roof - ceiling spaces and floor - <br />ceiling spaces. Irrespective of section 708.4, each tenant space shall be protected by no less than <br />one -hour fire resistance protection extending to the underside of the floor or roof deck above. <br />There will be no roof penetrations within 4 feet of either side of the fire partition. <br />Section 709.11 is added to read as follows: <br />709.11 Fire partitions. In a building or portion of a building of a mixed use B or M occupancy <br />classification, when enclosed spaces are provided for separate tenants, such spaces shall be <br />separated by not less than 1 -hour fire resistance. <br />Section 903.1 is amended by adding the following: <br />903.1.2 More restrictive section applies. Where fire sprinklers are required in other sections of <br />this code, the most restrictive requirement will apply to methods of construction, installation, or <br />other system requirements. <br />Section 903 is amended by adding the following: <br />903.2.12.6 Other occupancy classifications. An automatic sprinkler system shall be provided <br />throughout all buildings classified as Group B or Group F -2 having a fire area exceeding 18,000 <br />square feet. <br />903.2.13.6 Additions and Expansions. Any building constructed after April 1, 2002 that exceeds <br />18,000 sq. ft. or any attached construction, alteration, or addition to an existing structure of any <br />group that causes the structure to exceed 18,000 sq. ft. For purposes of this section, an automatic <br />fire sprinkler system is to be installed in the non - conforming or existing structure in addition to <br />the new construction area. <br />Section 903.4 Exception 3 is deleted. <br />Sections 1507.8 and 1507.9 are deleted and replaced with the following: <br />1507.8. Wood shingles and shakes are prohibited as new or replacement roofing material, except <br />that would shingles and shakes as the primary roofing surface in existence on January 1, 2001 <br />may be replaced with UL listed fire retardant shingles or shakes that are approved by the fire <br />marshal. <br />Section 3001 is amended by adding the following: <br />3001.5 If there is a conflict between state law, the International Building Code or local code <br />amendments, the most restrictive provision shall apply. <br />Section 3305 is amended by adding the following: <br />3305.2 Contractors shall ensure that every construction, remodel, repair, or renovation site has a <br />method of containment for trash and debris. The contractor shall ensure that the trash and debris <br />