<br />requirements of subsection (b) or not be less than the required flow of the sprinkler system plus <br />250 gpm. <br /> <br />(d) The flow requirements listed in this section shall be met with a minimum of 20 pounds per <br />square inch residual. This residual must be maintained in residential, commercial, and industrial <br />areas. Flow in residential areas is to be calculated at 1.5 gpm per living unit. <br /> <br />(e) If the fire code official determines that an occupancy is of a hazardous nature, or if special <br />hazards exist in addition to the normal hazard of the occupancy, section 901 of the International <br />Fire Code shall apply. <br /> <br />Section 508.5 is amended to read as follows: <br /> <br />508.5. Fire hydrant systems. <br /> <br />(a) A fire hydrant is a national standard three-way hydrant connected to six-inch or larger water <br />mams. <br /> <br />(b) A two-way hydrant is not recognized unless it was installed before January 1, 1985 or it was <br />installed in conjunction with nationally approved sprinkler systems. <br /> <br />(c) Fire hydrants shall conform to the A WW A Standard for Dry Barrel Fire Hydrants, C-502-85. <br /> <br />(d) Fire hydrants shall have one 4.5 inch steamer and two 2.5 inch side connections with <br />National Standard threads. The centerline ofthe steamer connection shall be a minimum of 18 <br />inches above the ground surface. <br /> <br />(e) Hydrants must be located so that no portion of any new structure is more than 500 feet, as the <br />hose lies, on accessible approved roadways. <br /> <br />(f) Hydrants shall be spaced no less than every 500 feet in residentially zoned areas and no less <br />than one every 300 feet in commercially and industrially zoned areas. <br /> <br />(g) The engineering department shall have the authority to develop and approve new fIfe hydrant <br />installation methods and standards consistent with the application of this section. <br /> <br />(h) Hydrants shall be installed in accordance with local jurisdiction construction standards. <br /> <br />Section 508.5.1 is amended to read as follows: <br /> <br />508.5.1 Where required. Where a portion of the facility or building hereafter constructed or <br /> <br />- 7 - <br />