<br />RFP 24-057 <br /> <br />I 3.02 <br /> <br />3.03 <br /> <br />I <br /> <br />587 -0702 <br /> <br />INSTALLATION OF DUCTWORK <br /> <br />A. General: Assemble and install ductwork in accordance with recognized industry <br />practices which will achieve air-tight and noiseless (no objectionable noise) systems, <br />capable of performing each indicated service. Install each run with minimum <br />number of joints. Align ductwork accurately at connections, within 1/8-inch <br />misalignment tolerance and with internal surfaces smooth. Support ducts rigidly with <br />suitable ties, braces, hangers, and anchors of type which will hold ducts true-to- <br />shape and to prevent buckling. Support vertical ducts at every floor or as <br />recommended by manufacturer. <br /> <br />B. Field Fabrication: Complete fabrication of work at project as necessary to match <br />shop-fabricated work and accommodate installation requirements. <br /> <br />C. Routing: Locate ductwork runs as indicated in the plans. <br /> <br />D. Coordination: Coordinate duct installations with installation of accessories, <br />dampers, equipment, controls, weir area covers, and other associated work of <br />ductwork system. <br /> <br />FIELD QUALITY CONTROL <br /> <br />Any ductwork found to be improperly installed will be removed and replaced with ductwork, <br />liner or fittings meeting these specifications. Improper installation will include, but not be <br />limited to, the following: <br /> <br />A. Fiberglass duct smaller than specified. <br /> <br />B. Construction joints not properly sealed. <br /> <br />3.04 EQUIPMENT CONNECTIONS <br /> <br />General: Connect ductwork to equipment as indicated, provide flexible connection for <br />each ductwork connection to equipment mounted on vibration isolators, and/or equipment <br />containing rotating machinery. Provide access doors as indicated. <br /> <br />3.05 ADJUSTING AND CLEANING <br /> <br />I <br /> <br />A. Clean ductwork internally, unit by unit as it is installed, of dust and debris. Clean <br />external surfaces of foreign substances which might cause corrosive deterioration of <br />fiberglass or, where ductwork is to be painted, might interfere with painting or cause <br />paint deterioration. <br /> <br />B. <br /> <br />Temporary Closure: At ends of ducts which are not connected to equipment or air <br />distribution devices at time of ductwork installation, provide temporary closure of <br />polyethylene film or other covering which will prevent entrance of dust and debris <br />until time connections are to be completed. <br /> <br />15892-8 <br />