<br />SAND AND GREASE <br /> <br />Grease, oil and sand interceptors shall be provided when wastes <br />containing these pollutants are discharged into the sanitary sewer <br />system of the City. Interceptors shall not be required on private <br />dwellings. Grease, oil and sand interceptors shall be sized and <br />designed according to the criteria contained in this section. <br /> <br />Design Criteria: <br /> <br />Grease, oil and sand interceptors shall be sized in accordance with <br />the Uniform Plumbing Code. The interceptor shall have two <br />compartments with the primary having a seven (7) minute detention time <br />and the secondary having a five (5) minute detention time. The <br />interceptor shall have access into each compartment for the purpose of <br />cleaning. The interceptor shall be constructed of impervious material <br />acceptable to the City of San Marcos. The interceptor shall be <br />capable of withstanding the traffic load where installed. All piping <br />entering, within, and exiting the interceptor shall be installed <br />according to the attached diagram. <br /> <br />Manufactured interceptors acceptable to the Director and properly <br />sized may be used in lieu of on site construction. Where possible, <br />the interceptor shall be installed outside the building. <br /> <br />Sizing Criteria: <br /> <br />Grease, oil and sand interceptors shall be sized according <br />following criteria: <br /> <br />to <br /> <br />the <br /> <br /> TRAP AND TRAP <br />KIND OF FIXTURE ARM SIZE FIXTURE UNIT <br />3 compartment sink 1 1/211, 2. 3, 4 <br />2 compartment sink 1 1/28 1 <br />Dishwasher 2" 4 <br />Garbage grinder 28 4 <br />Wok stove 2" 4 <br />Floor Drains (28, 38, 48) 2., 38, 48 2, 3, 4 <br />*Floor Sinks (3", 48) 3., 48 3, 4 <br /> <br />*Note: For indirect waste systems where hub drains and floor sinks <br />are used as receptors for dishwashers, 2 and 3 compartment sinks, etc. <br />the fixture unit count shall be twice (2X) the trap arm size. <br /> <br />Mop sink and hand sinks may be required to drain through a sand and <br />grease interceptor, but shall not be included for interceptor sizing <br />since they should not effect the grease loading on the interceptor. <br /> <br />-17- <br />