Section 903.2.10; change to read as follows: <br />903.2.10 Group S-2 enclosed parking garages. An automatic sprinkler system shall be provided <br />throughout buildings classified as enclosed parking garages in accordance with Section 406.4 of <br />the International Building Code or where located beneath other groups. <br />Section 903.2.11; change 903.2.11.3 and add 903.2.11.7, 903.2.11.8, and 903.2.11.9 as follows: <br />903.2.11.3 Buildings SS feet or more in height. An automatic sprinkler system shall be installed <br />throughout buildings that have one or more stories with an occupant load of 30 or more other than <br />penthouses in compliance with Section 1510 of the International Building Code, located 55 feet <br />(16 764mm) or more above the lowest level of fire department vehicle access, measured to the <br />finished floor. <br />Exceptions: <br />1. Open parking structures in compliance with Section 406.5 of the International Building <br />Code having no other occupancies above the subject garage. <br />2. Occupancies in Group F-2. <br />903.2.11.7 High -Piled Combustible Storage. For any building with a clear height exceeding 12 <br />feet (4572 mm) see Chapter 32 to determine if those provisions apply. <br />903.2.11.8 Spray Booths and Rooms. New and existing spray booths and spraying rooms shall <br />be protected by an approved automatic fire -extinguishing system. <br />903.2.11.9 Buildings Over 6,000 sgft. An automatic sprinkler system shall be installed <br />throughout all buildings with a building area 6,000 sq. ft. or greater and in all existing buildings <br />that are enlarged to be 6,000 soft. or greater. For the purpose of this provision, fire walls shall <br />not define separate buildings. <br />Exception: Open parking mages in compliance with Section 406.5 of the International <br />BuildingCode. <br />Section 903.3.1.2.3; add section to read as follows: <br />Section 903.3.1.2.3 Attics and Attached Garages. Sprinkler protection is required in attic spaces <br />of such buildings three or more stories in height, in accordance with NFPA 13 and or NFPA 13R <br />requirements, and attached garages. <br />Section 903.3.1.2.4; add section to read as follows: <br />Section 903.3.1.2.4 Exterior closets. Sprinkler protection shall be provided in closets (regardless <br />of size) that are accessible from the exterior of the building. <br />Section 903.3.1.4; add to read as follows: <br />