Laserfiche WebLink
<br />Three hase three and four wire 120/240 volt delta wirin s stems <br />ABC N <br />Red Oran e Black White <br /> <br />277/480 volt or 480 volt delta wiring systems <br />A B C N <br />Brown Yellow Purple Gray/White <br /> with 1 or <br /> more colored <br /> stripes <br /> <br />(16) Every light pole ten feet above adjacent grade shall have an eight foot ground rod. <br /> <br />(17) Labeling: <br /> <br />(A) Meter sockets shall be labeled with the business address, house number, apartment <br />number, lot number or duplex number ofthe unit to which the meter socket is connected. <br /> <br />(B) At the time of final inspection, the meter sockets shall be labeled with permanent labels <br />that are of such a quality that the readability of the labels will not be affected by the <br />environment. A list of acceptable marking and labeling devices is available at the San Marcos <br />Electrical Utility Department. <br /> <br />(18) Sub-metering of electrical service is prohibited. <br /> <br />(19) The service mast shall have at least two points of attachment to the building. One <br />point of attachment must be within 12 inches of the service equipment. The service <br />equipment may not be used to meet this requirement. <br /> <br />Sees. 14.293--14.320. Reserved. <br /> <br />Sec. 14.321 Board of adjustments and appeals. <br /> <br />The Construction Board of Appeals established in Section 14.026, will hear and decide appeals of <br />orders, decisions or determinations made by the building official relative to the application and <br />interpretation of this code. <br /> <br />Sees. 14.322-14345. Reserved. <br /> <br />DIVISION 4. ELECTRICAL INSPECTOR <br /> <br />Sec. 14.346. Qualifications and appointment. <br /> <br />The building official will appoint the electrical inspector. The building official will serve as the chief <br />electrical inspector. <br /> <br />Sec. 14.347. Duties. <br /> <br />29 <br />