<br />The exception to Section 603.4 is amended to read as follows: <br /> <br />Exception: Unvented fuel-fired heaters that are listed and approved for installation <br />in one- and two-family dwellings may be used therein. <br /> <br />Section 604.2.14.3 is amended to read as follows: <br /> <br />604.2.14.3. Emergency systems. Exit signs, exit illumination as required by Chapter <br />10, and elevator car lighting are classified as emergency systems and shall operate <br />within 10 seconds of failure of the normal power supply for egress lighting and shall <br />be capable of being transferred to the standby source. <br /> <br />Section 605.5.1 is amended to read as follows: <br /> <br />605.1.1. Power supply. Extension cords shall be plugged directly into an approved <br />receptacle and, except for approved multi plug extension cords, shall serve only one <br />portable appliance. <br /> <br />Section 605.9 is amended to read as follows: <br /> <br />605.9. Temporary wiring. Temporary wiring for electrical power and lighting <br />installations is not allowed to exceed a period of 90 days. Temporary wiring methods <br />shall meet the applicable provisions of the ICC International Electrical Code or <br />National Electrical Code as adopted. Temporm"y wiring for construction purposes <br />shall be removed at the end of construction. <br /> <br />Section 605 is amended by adding the following: <br /> <br />605.10. Labels for disconnecting means. Each disconnecting means for each service <br />feeder, or branch circuit shall be legibly marked to indicate its purpose at the point <br />where it originates. Where the service feeder or branch is located on a building or <br />other structure, a description of the device and address of the building must be <br />prominently displayed utilizing a marking of sufficient durability to withstand the <br />environment involved. A list of acceptable marking devices and labels can be <br />obtained through the electric utility department. <br /> <br />Section 903.1.1 is amended to read as follows: <br /> <br />903.1.1. An approved automatic fire sprinkler system meeting the requirements of <br />section 903 shall be installed in buildings as follows: <br /> <br />C:\TEMP\mark's fire code 2-6-02.doc <br /> <br />- 9- <br />