<br />d. Acceptable manufacturers: <br />1) Allen Bradley. <br />2) Toshiba International Corporation. I <br />3) Robicon. <br />e. Output rating 3-phase; 6 to 66 Hz, with torque constant as speed <br />changes. <br />f. Unit Operating Requirements: <br />1) Input AC voltage tolerance of 380 to 500 V, plus or minus <br />10 percent. <br />2) Input frequency tolerance of 50/60 Hz, plus or minus 6 percent. <br />3) Capable of driving full load, under the following conditions, without <br />derating: <br />i. Ambient Temperature: 0 to 40oC. <br />ii. Humidity: Less than 90 percent (non-condensing). <br />iii. Altitude: 3300 feet. <br />4) Minimum Efficiency: 96 percent at 60 Hz, full load. <br />5) Minimum Displacement Primary-Side Power Factor: 96 percent. <br />6) Overload Capability: 1.1 times the base load current for 60 <br />seconds, 2.0 times the base load current for 3 seconds. <br />7) Starting Torque: 100 percent of rated torque or as indicated. <br />8) Speed Regulation: Plus or minus 1 percent. <br />9) Isolated control interface to allow controller to follow control signal <br />over an 11:1 speed range. <br />g. Internal Adjustability Capabilities: <br />1) Minimum Speed: 5 to 25 percent of maximum rpm. <br />2) Maximum Speed: 80 to 100 percent of maximum rpm. I <br />3) Acceleration: 2 to a minimum of 22 seconds. <br />4) Deceleration: 2 to a minimum of 22 seconds. <br />5) Current Limit: 50 to a minimum of 110 percent of maximum rating. <br />h. Self-Protection and Reliability Features: <br />1) Input transient protection by means of surge suppressors. <br />2) Snubber networks to protect against malfunction due to system <br />voltage transients. <br />3) Under- and over-voltage trips; inverter overtemperature, overload, <br />and overcurrent trips. <br />4) Motor Overload Relay: Adjustable and capable of NEMA 250, <br />Class 20 performance. <br />5) Notch filter to prevent operation' of the controller-motor-Ioad <br />combination at a natural frequency of the combination. <br />6) Instantaneous line-to-Iine and line-to-ground overcurrent trips. <br />7) Loss-of-phase protection. <br />8) Reverse-phase protection. <br />9) Short-circuit protection. <br />10) Motor overtemperature fault. <br />i. Multiple-Motor Capability: Controller suitable for service to multiple <br />motors and having a separate overload relay and protection for each <br />controlled motor. Overload relay will shut off controller and motors <br />served by it when overload relay is tripped. <br />J. Automatic Reset and Restart: To attempt three restarts after controller I <br />fault or on return of power after an interruption and before shutting down <br />for manual reset or rotating loads spinning in either direction and <br />