<br /> } J-ql} r <br /> WIL1ÈL <br /> Municipal Building <br /> Environmentals and <br /> SITE INSTALLATION REQUIREMENTS <br /> (For Meridian 1) <br /> Your telephone system's switching network is a modern electronic device and, like <br /> any other such equipment, requires controlled housing space with the proper <br /> environmental requirements. <br /> These requirements are extremely important and, to expect a trouble free system, <br /> MUST be satisfied. <br /> A. PHYSICAL SPACE <br /> The space required is dependent upon the shape of the room and clearances <br /> needed in front of existing electrical panels and other existing <br /> equipment. The figure stated is an average and is intended to be used for <br /> estimating purposes only. The exact floor plan must be drawn by WilTel <br /> Engineering before a firm room dimension can be specified. (A general <br /> starting point is 6' x 8'). <br /> CDR Processors can be located in the Equipment Room; however, it is <br /> usually more convenient to the operator to ~ocate this in an office. <br /> This equipment will sit on a 24 inch by 48 inch table. Additional space <br /> will be needed if the processor is to reside in the Equipment Room. <br /> The preliminary room size needed for the proposed equ~ment is 10 X 17. <br /> Space can be saved in the Equipment Room by placing the Batteries (if <br /> provided) in another room. This room should be 100 feet or less from the <br /> Equipment Room. The ideal temperature for batteries is 77"F. <br /> The switch room floor should not be carpeted or have an unsealed cement <br /> surface. No activities should be undertaken in the switch room which may <br /> generate dust. There should be no storage of articles within the space as <br /> to obstruct airflow into and out of the switch room. Care should be <br /> exercised at all times not to obstruct air flow in and around the switch. <br /> The floor must be capable of supporting minimum bearing loading of 128 <br /> lbs/sq. ft. Special loading considerations may be required when batteries <br /> and rectifier equipment are to be ïnstalled. The room should also be <br /> subject to minimum vibrations (less than 0.5 g at 400 HZ). <br /> Ceiling height should be a minimum of 8 feet. <br /> B. ENVIRONMENT <br /> SL-l Set (QSU60) OaF to 86°F, 20 - 80% RH <br /> SL-l Cabinets OaF to 77°F, 20 to 80% RH Absolute Limits <br /> 59°F to 72°F, 20 to 55% RH Recommended <br /> Dust density should be Zone 4 (0.00014 g/m3) or better. <br /> Average residential dust density is Zone 3 (.00030 g/m3). <br /> The room must be well lit and meet security requirements. <br /> Customer: ¡4;~ e <br /> Revised 9/24/94 Page 1 of 10 WilTel: CA~! <br />