<br />RFP 24-057 <br /> <br />10. <br /> <br />11. <br /> <br />587-0702 <br /> <br />8. <br /> <br />Provide heaters for air and water as needed for proper operation of the <br />biological treatment unit. <br />Minimum required airflow rate has been given. If fresh air dilution is required <br />for the proper functioning of the odor control system, the PROPONENT will <br />ensure the airflow given will be increased by that amount. <br />Provide stairs to access media surface on biofilters if media surface is above <br />grade. <br />All drains from a pressure area will include a trap with c1eanout. Trap will <br />contain a depth of water sufficient to prevent escape of foul air from the <br />system. <br /> <br />9. <br /> <br />B. Structure or vessel: All materials used in the structure or vessel will be inherently <br />corrosion resistant or will have a corrosion resistant coating. Design drawings for <br />structure(s) and vessel(s) will be sealed by a licensed engineer of the State of Texas. <br />Acceptable materials include: <br /> <br />I <br /> <br />1. High density polyethylene (HOPE); <br />2. Fiberglass Reinforced Plastic (FRP) construction: Provide a gel coat on all <br />surfaces and UV inhibitor on all external surfaces. Comply with the <br />requirements of specification section 15160 - FRP Chemical Storage Tanks. <br />3. Portland Cement Concrete: If the PROPONENT proposes the use of <br />concrete basins to contain its media, the CITY will provide these basins. I <br />The anticipated cost to the CITY of providing these basins will be considered <br />in the evaluation of the PROPONENT's proposal; <br />4. Grade 316L stainless steel; <br />5. Hastelloy C; <br />6. Polyvinyl Chloride (PVC). <br />7. Other materials may be utilized on a case-by-case basis subject to approval <br />by CITY and its engineer. <br />PROPONENT will evaluate the need for covering or enclosing the odor control unit <br />and provide a cover or enclosure if necessary. Evaluation will include ambient and <br />process temperatures and wind conditions. Media will be of sufficient size and <br />weight so as to not become airborne under windy conditions or a cover or <br />enclosure will be provided to retain media. If required, the cover or enclosure shall <br />be of materials listed as acceptable for the structure or vessel. <br /> <br />C. Blowers: <br /> <br />1. <br /> <br />A system with a minimum of three (3) blowers with VFDs, two (2) duty units <br />and one (1) standby unit is required for the odor control treatment system at <br />the WWTP. Remote systems will have a set of two (2) blowers one (1) duty <br />and one (1) standby. No VFDs are required for the remote system blowers. <br />All surfaces exposed to corrosive or treated airstream will utilize corrosion <br />resistant materials. Supplier is responsible for adequately sizing the blower <br />to meet the specified flow rates, considering the pressure loss through the <br />scrubber and duct system. The blower will be sized to overcome the loss <br />through the complete system including suction piping from the odor sources. <br />At the connection to the odor system ductwork, SUPPLIER will assume that <br /> <br />2. <br /> <br />11 065-9 <br /> <br />I <br />