<br /> 174 <br /> RAMON LUCIO, RIO VISTA, RIO VISTA ANNEX, AND BICENTENNIAL <br /> PARKS RECREATION DEVELOPMENT <br /> TECHNICAL SPECIFICATION 11 <br /> RESTROOM BUILDINGS <br /> (3) At the finish of the work, this Contractor shall <br /> furnish the OWner a certificate showing the acceptance of the work <br /> done under his contract by the local inspector and payment of <br /> inspection fees. <br /> b. Codes: The 1987 National Electrical Code, the 1988 and <br /> 1989 supplements thereto shall be recognized aa a minimum <br /> acceptable standard for work under these specifications, Bee <br /> Section 9. The City of San Marcos has local supplements to the <br /> code which affect the construction. These are aa follows: <br /> (1) All services less than 600 amps shall have outside <br /> disconnects. <br /> (2) Electrical Ketalic Tubing shall not be allowed under <br /> concrete. <br /> (3) Minimum wire size for all applications shall be #12 <br /> AWG. Aluminum wire less than #6 AWG shall not be allowed for any <br /> application. Copperclad wires shall not be allowed for any <br /> application. <br /> (4) Non residential electrical wiring of all types shall <br /> be in conduit. <br /> (5) All underground wiring shall be in conduit. <br /> (6) Romex cable shall not be used for non-residential <br /> construction. <br /> c. Service Connections: Electrical service will be brought <br /> in and installed as shown on the drawings. The electrical <br /> Contractor shall furnish and install the necessary switches, <br /> panels, wire, conduit, etc., as required for a complete <br /> installation. Thia Contractor shall verify location and type of <br /> service at the site. <br /> 11-26 <br />